Standard Series ACP - 5 to ACP - 30

Portable ChillersTemperature Corporation manufactures the Standard Series of chillers from ACP - 5 to ACP - 30. Our standard series of portable chillers can be moved from one piece of process equipment to another using casters. With a single compressor, the standard portable chiller is a mid-sized model that offers medium capacity cooling of 5 tons to a maximum of 30 tons at 50° F leaving water temperature at 95 F plant air temperature. Temperature range is from 20° F to 60° F leaving water temperature.

  • Our unique design has the components accessible for inspection, maintenance and service.
  • Our chillers come standard with hot gas by-pass for capacity control.
  • For freeze protection we include both a water flow switch and a freeze thermostat.
  • Stainless steel frame, tank and pump.
  • We use a stainless steel brazed plate evaporator for cooling, not an inefficient coil-in-tank which is very difficult to repair and extremely expensive to replace.

Main Features

COMPRESSOR
The standard portable chiller comes with a single scroll compressor that ranges from 5 to 30 hp and comes with a hot gas by-pass for two (2) steps of capacity control, 100%, 50% and off.

EVAPORATOR
The evaporator for the standard portable chiller features a 5 to 30 ton stainless steel copper brazed plate chiller vessel with an outlet freeze thermostat, water flow switch and return line bronze "Y" strainer.

CONDENSER
The condenser is a 5 to 30 ton indoor air cooled condenser with copper tubes and aluminum fins with a top discharge propeller fan direct coupled to the fan motor.

TANK
The tank for the dual is a 16 gauge stainless steel welded tank complete with ½" armaflex insulated tank, an 1 ¼" clear plastic water level - fill tube with vent cap, side bottom drain with shut-off valve and a return line shutoff valve. Tank capacities range from 15 gallons to 90 gallons.

PUMP
The standard model comes with a stainless steel pump up to a 5 hp close coupled to a 3500 rpm ODP motor and cast iron pump with bronze impeller 7.5 hp and up, pumps complete with non-ferrous piping with a bronze suction shutoff valve, suction hose for pump removal, a discharge PVC sch. 80 piping and pump discharge pressure gauge with shutoff valve. TEFC motors, discharge pressure operated water by-pass valve and dual pumps are optional.

CONTROLS
The controls for the standard chiller consist of a two (2) or four (4) stage solid state digital temperature controller with adjustable set points, refrigeration high and low pressure safeties, run and fail lights and compressor and fan motors internal thermal overload protection in winding.

FREEZE PROTECTION
The standard chiller uses both a flow switch and a freeze thermostat.

COMPONENTRY
Other notable components include a refrigeration expansion valve, sight glass moisture indicator, filter dryer, liquid line solenoid with shutoff valve, a hot gas solenoid with shutoff valve and a compressor crankcase heater.

FRAME SIZE
Chiller base frame is fabricated from 12 ga. stainless steel welded with 5" casters: two swivel, two rigid.

VOLTAGE
All models 230/460/575V, 3 phase, 60 hertz and 380V, 3 phase, 50 hertz.

What is a chiller? To learn more about industrial chillers click here.

In the interest of continuous improvement, Temperature Corporation reserves the right to change specifications without notice. While every effort is made to ensure accuracy, Temperature Corporation accepts no responsibility or liability resulting from the use of this information. Jan to Dec 2016.

Contact us today: Tel: 905.513.8310 - Email:

For your convenience we now offer payment options by:

Methods of Payment

Temperature Corporation, 111 Esna Park Drive, Unit 7, Markham, Ontario, L3R 1H2
Toll Free: 1.877.513.8310 ~ Email: